Ascon Tecnologic - KM3 - L - ENGINEERING MANUAL - PAG. 10
[36] oP.SL - Operating display selection
Available: always
Range: 0 = PV (upper display) and SP (lower display)
1 = SP only.
Note: Setting [36] oP.SL equal to 1, the instrument will not
shows the measured value and, in operator mode, the
upper display will be blank.
[37] SPLL - Minimum set point value
Available: always.
Range: From -1999 to [38] SPHL engineering units.
Note: When you change the [37] SPLL value, the instrument
checks the local set points (SP parameters). If SP
is out of this range, the instrument forces it to the
maximum acceptable value
[38] SPHL - Maximum set point value
Available: always.
Range: From [37] SPLL to 9999 engineering units.
Note: For other details see [37] SPLL parameter.
[39] SP - Set Point 1
Available: always.
From [37] SPLL to [38] SPHL engineering units.
[40] diS - The way of confi rming operation
Available: always.
Range: but = by keyboard
di = by digital input.
[41] tim - time duration of the last exceeded periode
Available: always but it is a read only parameter.
Range: from 00.00 to 99.59 (hh.mm);
[42] Hi- maximum measured value
Available: when [33] Hi.Lo = Hi (high limit alarm) but it is
a read only parameter.oFF - derivative action
excluded;
[43] Lo – minimum measured value
Available: Available: when [33] Hi.Lo = Lo (low limit alarm)
but it is a read only parameter.
Range: Engineering unit within the input range
]PAn group - Operator HMI
[44] PAS2
- Level 2 password: Limited access level
Available: Always.
Range: oFF = Level 2 not protected by password
(as level 1 = Operator level);
1 to 200.
[45] PAS3
- Level 3 password:
Complete confi guration level
Available: Always.
Range: 3 to 200.
Note: Setting [144] PAS2 equal to [45] PAS3, the level 2 will
be masked.
[46] di.CL - Display colour
Available: Always.
Range: 0 = The display colour is used to show the
exceed condition;
When no exceed condition is present, the
upper display will be green.
When an exceed condition (hi or low) is
detected, the upper display will be red.
1 = Display red (fi x);
2 = Display green (fi x);
3 = Display orange (fi x).
[47] diS.t - Display time out
Available: Always.
Range: oFF = The display is ever ON;
0.1 to 99.59 minutes and seconds.
Note: This function allows to turn OFF the display when no
alarm is present and no action is made on the instrument.
When diS.t is different from OFF and no button is
pressed for more than the programmed time out, the
display goes OFF and only 4 segments of the less
signifi cant digit are turned ON in sequence in order to
show that the instrument is working correctly.
If an alarm occures or a buton is pressed, the display
will come back to the normal operation.
]Ser group - Serial link parameter
[48] Add - Instrument address
Available: Always.
Range: oFF = Serial interface not used;
1 to 254.
[49] bAud - Baud rate
Available: When [131] Add different from oFF.
Range: 1200 = 1200 baud;
2400 = 2400 baud;
9600 = 9600 baud;
19.2 = 19200 baud;
38.4 = 38400 baud.
]CAL group - User calibration group
This function allows to calibrate the complete measuring
chain and to compensate the errors due to:
Sensor location;
Sensor class (sensor errors);
Instrument accuracy.
[50] A.L.P - Adjust Low Point
Available: Always.
Range: -1999 to (AH.P - 10) engineering units.
Note: The minimum difference between AL.P and AH.P is
equal to 10 Engineering Units.
[51] A.L.o - Adjust Low Offset
Available: Always.
Range: -300 to +300 engineering units.
[52] A.H.P - Adjust High Point
Available: Always.
Range: From (AL.P + 10) to 9999 engineering units.
Note: The minimum difference between AL.P and AH.P is
equal to 10 Engineering Units.
[53] A.H.o - Adjust High Offset
Available: Always.
Range: -300 to +300 Engineering Units.
Example: Environmental chamber with an operative range:
10 to 100°C.
1. Insert in the chamber a reference sensor connected with
a reference instrument (usually a calibrator).
2. Start the control of the instrument, and set a set point equal to
the minimum value of the operative range (e.g.: 10°C). When
the temperature in the chamber is steady, take note of the
temperature measured by the reference system (e.g.: 9°C).