107
Electrical Data ACK-E-2009
Electrical Data - Heat Pump (R22)
MODEL
INDOOR UNIT ACK 40ER ACK 40ER
OUTDOOR UNIT ALC 35CR ALC 40CR
INDOOR MOTOR
INSULATION GRADE CLASS B CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 176 176
RATED RUNNING CURRENT A 0.79 0.79
MOTOR OUTPUT W 60 60
POLES 66
OUTDOOR MOTOR
INSULATION GRADE CLASS B CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 220 220
RATED RUNNING CURRENT A 1.02 1.02
MOTOR OUTPUT W 145 145
POLES 88
COMPRESSOR
INSULATION GRADE --
POWER SOURCE - 1Ø / <3Ø> V/Ph/Hz
220 - 240 / 1 / 50 /
<380 - 415 / 3 / 50>
220 - 240 / 1 / 50 /
<380 - 415 / 3 / 50>
CAPACITOR - 1Ø / <3Ø> μF 60 60 / <NIL>
RATED INPUT POWER (COOLING) - 1Ø / <3Ø> W 2614 3054 / <2864>
RATED INPUT POWER (HEATING) - 1Ø / <3Ø> W 2354 2854 / <2804>
RATED RUNNING CURRENT (COOLING) -
1Ø / <3Ø>
A 12.6 14.9 / <5.2>
RATED RUNNING CURRENT (HEATING) -
1Ø / <3Ø>
A 11.6 14.1 / <5.4>
LOCKED ROTOR AMP. - 1Ø / <3Ø> A 114 114 / <48>
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
MODEL
INDOOR UNIT ACK 50ER
OUTDOOR UNIT ALC 50CR
INDOOR MOTOR
INSULATION GRADE CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
RATED INPUT POWER W 221
RATED RUNNING CURRENT A 0.97
MOTOR OUTPUT W 100
POLES 6
OUTDOOR MOTOR
INSULATION GRADE CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
RATED INPUT POWER W 220
RATED RUNNING CURRENT A 1.02
MOTOR OUTPUT W 145
POLES 8
COMPRESSOR
INSULATION GRADE -
POWER SOURCE V/Ph/Hz 380 - 415 / 3 / 50
CAPACITOR μF NIL
RATED INPUT POWER (COOLING) W 4159
RATED INPUT POWER (HEATING) W 3629
RATED RUNNING CURRENT (COOLING) A 7.3
RATED RUNNING CURRENT (HEATING) A 6.5
LOCKED ROTOR AMP. A 56
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
10_Electrical Data_A.indd 10710_Electrical Data_A.indd 107 4/6/2009 3:41:28 PM4/6/2009 3:41:28 PM