Application Information ACK-E-2009
Short Duct Speci cation
The indoor unit is provided with air discharge and air intake “knock-out” hole for duct connection. However
the connection of the short duct for air discharge is possible on only one side.
The use of short duct for air discharge will improve air ow distribution if there is an obstruction (such as
alighting xture) or in a long, narrow room or an L-shaped room. It is also used for air-conditioning of two
rooms simultaneously.
Possible Direction For Air Discharge and Air Intake
Possible Opening Dimension for Duct Connection
Note: 1. Avoid to use the short duct on which the air discharge grille can be completely closed, to
prevent evaporator freezing.
2. In order to prevent condensation forming, be sure that there is suf cient thermal insulation
and no leakage of cool air when installing the short duct.
3. Keep the introduction of fresh air intake within 20% of total air ow. Also provide a chamber
and use a booster fan.
Air Intake
Air DischargeAir Discharge