28
ACK-E-2009 Application Information
(6) Additional Charge
The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional
refrigerant charge after vacuuming is not necessary.
When the piping length is more than 7.6m, please use the table below (unit in gram).
R22
Model 10m 12m 15m 25m 35m 45m
20C/CR 38 / 53 70 / 96 118 / 162 - - -
25C/CR 94 / 53 172 / 98 289 / 164 - - -
28C/CR 94 / 133 172 / 244 291 / 411 - - -
30C/CR 133 / 133 244 / 243 410 / 409 964 / 961 1518 / 1514 2072 / 2067
35C/CR 130 / 136 238 / 248 400 / 418 940 / 983 1481 / 1547 2021 / 2112
40C/CR 134 / 136 245 / 248 412 / 418 968 / 983 1525 / 1547 2081 / 2112
50C/CR 130 / 134 238 / 245 400 / 412 942 / 968 1483 / 1525 2024 / 2081
R410A
Model 10m 15m 20m 25m 35m 45m
20C/CR 24 / 40 44 / 73 74 / 123 - - -
25C/CR 24 / 23 45 / 43 75 / 72 - - -
28C/CR 58 / 91 106 / 167 178 / 281 - - -
35C/CR 65 / 98 118 / 180 199 / 303 469 / 712 738 / 1122 1007 / 1531
40C/CR 61 / 97 112 / 178 189 / 299 445 / 703 700 / 1107 956 / 1511
50C/CR 50 / 87 92 / 159 155 / 267 363 / 628 572 / 989 781 / 1350
•
•