49
Engineering & Physical Data ACK-E-2009
General Data - Heat Pump (R410A)
MODEL
INDOOR UNIT A5CK 20ER A5CK 25ER
OUTDOOR UNIT A5LC 20CR A5LC 25CR
NOMINAL COOLING CAPACITY
Btu/h 18300 22200
W 5363 6506
NOMINAL HEATING CAPACITY
Btu/h 17700 20500
W 5188 6008
NOMINAL TOTAL INPUT POWER (COOLING) W 1740 1940
NOMINAL TOTAL INPUT POWER (HEATING) W 1490 1760
NOMINAL RUNNING CURRENT (COOLING) A 7.7 8.7
NOMINAL RUNNING CURRENT (HEATING) A 6.6 7.9
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
EER W/W 3.08 3.36
COP W/W 3.48 3.41
REFRIGERANT TYPE R410A R410A
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE OUTDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE
4 WAY AUTOMATIC LOUVER
(UP & DOWN)
4 WAY AUTOMATIC LOUVER
(UP & DOWN)
OPERATION
WIRELESS OR WIRED MICRO-
COMPUTER REMOTE CONTROL
WIRELESS OR WIRED MICRO-
COMPUTER REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 280 / 600 320 / 680
MEDIUM l/s / CFM 250 / 530 280 / 600
LOW l/s / CFM 200 / 430 250 / 530
EXTERNAL STATIC PRESSURE (H/M/L) Pa (in.wg.) 00
SOUND PRESSURE LEVEL (H/M/L) dBA 34 / 31 / 28 37 / 34 / 31
UNIT DIMENSION
( ) - WITH PANEL
HEIGHT mm/in 265 (340) / 10.43 (13.39) 265 (340) / 10.43 (13.39)
WIDTH mm/in 820 (990) / 32.3 (38.98) 820 (990) / 32.3 (38.98)
DEPTH mm/in 820(990) / 32.3 (38.98) 820(990) / 32.3 (38.98)
PACKING DIMENSION
( ) - PANEL
HEIGHT mm/in 300 (110) / 11.8 (4.33) 300 (110) / 11.8 (4.33)
WIDTH mm/in 916 (1030) / 36.1 (40.6) 916 (1030) / 36.1 (40.6)
DEPTH mm/in 916 (1030) / 36.1 (40.6) 916 (1030) / 36.1 (40.6)
WEIGHT (UNIT + PANEL) kg/lb 29+6 / 63.9+13.2 29+6 / 63.9+13.2
CONDENSATE DRAIN SIZE mm/in 19.1 / 3/4 19.1 / 3/4
OUTDOOR UNIT
AIR FLOW l/s / CFM 614 / 1300 755 / 1600
SOUND PRESSURE LEVEL dBA 52 52
UNIT DIMENSION
HEIGHT mm/in 654 / 25.7 756 / 29.8
WIDTH mm/in 855 / 33.7 855 / 33.7
DEPTH mm/in 328 / 12.9 328 / 12.9
PACKING DIMENSION
HEIGHT
mm/in 710 / 28.0 810 / 31.9
WIDTH mm/in 990 / 39.0 990 / 39.0
DEPTH mm/in 415 / 16.3 415 / 16.3
UNIT WEIGHT kg/lb 59 / 130 62 / 137
PIPE CONNECTION
TYPE FLARE VALVE FLARE VALVE
SIZE
LIQUID mm/in 6.4 / 1/4 6.4 / 1/4
GAS mm/in 12.7 / 1/2 15.9 / 5/8
REFRIGERANT CHARGE kg/lb 1.75 / 3.86 1.85 / 4.08
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW FASCIA.
07-General data_A.indd 4907-General data_A.indd 49 4/6/2009 11:13:11 AM4/6/2009 11:13:11 AM