52
ACK-E-2009 Engineering & Physical Data
General Data - Heat Pump (R410A)
MODEL
INDOOR UNIT A5CK 50ER
OUTDOOR UNIT A5LC 50CR
NOMINAL COOLING CAPACITY
Btu/h 43000
W 12603
NOMINAL HEATING CAPACITY
Btu/h 47300
W 13863
NOMINAL TOTAL INPUT POWER (COOLING) W 4390
NOMINAL TOTAL INPUT POWER (HEATING) W 4010
NOMINAL RUNNING CURRENT (COOLING) A 7.6
NOMINAL RUNNING CURRENT (HEATING) A 7.2
POWER SOURCE V/Ph/Hz 380 - 415 / 3 / 50
EER W/W 2.87
COP W/W 3.46
REFRIGERANT TYPE R410A
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE
4 WAY AUTOMATIC LOUVER
(UP & DOWN)
OPERATION
WIRELESS OR WIRED MICRO-
COMPUTER REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 570 / 1200
MEDIUM l/s / CFM 490 / 1030
LOW l/s / CFM 440 / 930
EXTERNAL STATIC PRESSURE (H/M/L) Pa (in.wg.) 0
SOUND PRESSURE LEVEL (H/M/L) dBA 47 / 44 / 43
UNIT DIMENSION
( ) - WITH PANEL
HEIGHT mm/in 300 (375) / 11.81 (14.76)
WIDTH mm/in 820 (990) / 32.3 (38.98)
DEPTH mm/in 820(990) / 32.3 (38.98)
PACKING DIMENSION
( ) - PANEL
HEIGHT mm/in 335 (110) / 13.19 (4.3)
WIDTH mm/in 916 (1030) / 36.1 (40.6)
DEPTH mm/in 916 (1030) / 36.1 (40.6)
WEIGHT (UNIT + PANEL) kg/lb 42+6 / 92.6+13.2
CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75
OUTDOOR UNIT
AIR FLOW l/s / CFM 2171 / 4600
SOUND PRESSURE LEVEL dBA 68
UNIT DIMENSION
HEIGHT mm/in 850 / 33.5
WIDTH mm/in 1030 / 40.6
DEPTH mm/in 400 / 15.8
PACKING DIMENSION
HEIGHT
mm/in 1000 / 39.4
WIDTH mm/in 1200 / 47.2
DEPTH
mm/in 560 / 22.1
UNIT WEIGHT kg/lb 105 / 232
PIPE CONNECTION
TYPE FLARE VALVE
SIZE
LIQUID mm/in 9.5 / 3/8
GAS mm/in 15.9 / 5/8
REFRIGERANT CHARGE kg/lb 2.3 / 5.07
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.5m BELOW FASCIA.
07-General data_A.indd 5207-General data_A.indd 52 4/6/2009 11:13:12 AM4/6/2009 11:13:12 AM