Page GB-28
2200..00
PPAARRAAMMEETTEERR 0044
Parameter 4 - Summer ECO-temperature*
Setting range: OFF, 10.0 to 30.0 °C
Factory setting: 20.0 °C
SSYYSSTT
°C
Note: The active summer ECO-temperature appears on the
standard display with a sunshade symbol.
Application: All objects which do not require heating opera-
tion during summer.
This parameter refers to the heating delimiting value and takes
the heating automatically out of service as soon as the outside
temperature exceeds the set heating delimiting value. During
summer ECO-temperature, the pumps are activated each day
for approx. 20 seconds and mix valves, if present, are opened
briefly to protect them against corrosion (anti-blocking protec-
tion).
With setting OFF summer switching-off is not in effect.
Hot water preparation is not affected by summer switching-
off.
6633..55
1166::3322
WWEE.. 2255.. JJUUNN..;;0033
°C
ÀÀ
Summer switching-off active
next parameter
22..00
PPAARRAAMMEETTEERR 1111
Parameter 11 - Return to standard display
Setting range: OFF, 0.5 to 5.0 minutes
Factory setting: 2.0 min
SSYYSSTT
min
After expiration of the specified time without any action the
system will automatically exit and return to the standard display.
next parameter
Note: The time set here applies for the buttons
¢¢
operating mode selection button
££
heating curve adjustment
¥¥
desired day room temperature
¦¦
desired reduced room temperature
§§
desired domestic hot-water temperature
as well as for the level selection (see programming
level) and the input of codes.
* only when the outside sensor is connected.
GB
8A521100_GB.qxd 10.11.2004 12:05 Seite 28