Specifications
Supply Voltage: 120/240 Vac, +10% -15%, 50/60 Hz
Setpoints:
Series 2000
: Analog - single-turn
potentiometer, 270° rotation
Series 3020
: Mechanical digital
potentiometer
Setpoint Repeatability: +/-0.3% of span (Series 2000)
Setpoint Resolution:
Series 2000
: 0.2% of span
Series 3020
: 1 °F or °C
Input: Thermocouple Types J, K, T, R (Series 2000)Types J, K
(Series 3020), range dependent.
Maximum lead resistance 100 ohms for rated accuracy;
cold junction compensation standard. RTD input 100 ohms
platinum at 0°C, DIN (.00385) curve.
Thermocouple
Break Protection: Built-in, failsafe, open sensor, output zero;
Meter units – upscale indication
Cold Junction
Compensation: Automatic electrical
Accuracy: +0.5% of span at calibration points
Indication,
Temperature: Deviation meter
+
50 °F (
+
30 °C) of setpoint
Load: LED on when power is supplied to load
Proportional Band: On/off or nominal 5 °F - 50 °F (3 °C - 30 °C)
Offset (Manual Reset): Adjustable over 100% of proportional band
Rate (Derivative): 0.5 to 25 seconds
Reset (Integral): 0.7, 1, 2 or 4 minutes via internal
DIP switches
Alarm: 3 A at 120 Vac
Output: B - SPDT Relay, non-inductive rated
7A/5A max at 120/240 Vac, 50 VA inductive
F - 4 to 20 mAdc into 1000 ohms max load
L - SPDT Relay, non-inductive rated
7A/5A max at 120/240 Vac, 50 VA inductive
S - 20 Vdc into 1000 ohm maximum load
T - 1 A solid-state relay; 10 A max. inrush
Ambient Temp Range: 30° to 130 °F (0 to 55° C)
Weight: 1 lb, 9 oz (709 g)
All specifications subject to change.