EPIC 2DGeneral use
ALARM WITH STOP PUMP
Following the detection of an alarm and the consequent blocking of the pump, the
control panel provides the following operations:
• Try the first restart after 5 min.
• In case of a negative result, make another attempt after 30 min. and 3 other
attempts with intervals of 60 min.
• After 5 attempts if the alarm persists, the control panel permanently blocks the
pump and the alarm remains active until the user intervenes.
DELETE ALARM
0
P1
0
P2
To delete the alarms, enter the “0” button for pump 1 once and the
“0” button for pump 2.
IMPORTANT!
If after having canceled the alarm, the same occurs again, an intervention on the
cause is necessary.