Maximum allowed current in function of the ambient temperature for installation method C
I 4 ¤
Ø Þ ç Ù Ù Þ
4
â Þ Ü
6
Ù à Ü Þ
C
6 ¤ 2
Þ
3
Þ
1
Ù Ø ß ç
>
N
C ©
N
C ©
@
N
C
@
N
C
@ @
N
C
4 mm² < 32 A < 28 A < 25 A < 23 A < 20 A
6 mm² < 41 A < 36 A < 32 A < 29 A < 25 A
10 mm² < 57 A < 50 A < 45 A < 40 A < 35 A
16 mm² < 76 A < 66 A < 60 A < 54 A < 46 A
25 mm² < 96 A < 84 A < 76 A < 68 A < 59 A
35 mm² < 119 A < 104 A < 94 A < 84 A < 73 A
50 mm² < 144 A < 125 A < 114 A < 102 A < 88 A
70 mm² < 184 A < 160 A < 145 A < 131 A < 112 A
95 mm² < 223 A < 194 A < 176 A < 158 A < 136 A
120 mm² < 259 A < 225 A < 205 A < 184 A < 158 A
Installation method F according table B.52.1.
Single-core cables, touching in free air
Clearance to wall not less than one cable diameter
Maximum allowed current in function of the ambient temperature for installation method F
I 4 ¤
Ø Þ ç Ù Ù Þ
4
â Þ Ü
6
Ù à Ü Þ
C
6 ¤ 2
Þ
3
Þ
1
Ù Ø ß ç
>
N
C ©
N
C ©
@
N
C
@
N
C
@ @
N
C
25 mm² < 110 A < 96 A < 87 A < 78 A < 67 A
35 mm² < 137 A < 119 A < 108 A < 97 A < 84 A
50 mm² < 167 A < 145 A < 132 A < 119 A < 102 A
70 mm² < 216 A < 188 A < 171 A < 153 A < 132 A
95 mm² < 264 A < 230 A < 209 A < 187 A < 161 A
120 mm² < 308 A < 268 A < 243 A < 219 A < 188 A
ê ò ó ÿ
ó ò
ë
ì ï
(
ë
ë î
ê
+
Single supply cables (3 phases + PE - configuration (1)):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables)
Install the prescribed fuse on each cable
Parallel supply cable (2 x 3 phases + PE - configuration (2)):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables) and divide
by 2
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 phases + PE as in (3):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables) and divide by ¥3
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Fuse size: the recommended maximum fuse size divided by ¥3 on each cable.
Size of the PE cable:
For supply cables up to 35 mm²: same size as supply cables