• For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).
ñ ò ì í ó ï
+
I
tot
= 89 A, maximum ambient temperature is 45 °C,
recommended fuse = 100 A
• Single supply cables (3 phases + PE - configuration (1)):
• I = 89 A + 10 % = 89 x 1.1 = 97.9 A
• The table for B2 and ambient temperature = 45 ° C allows a maximum current of 93 A for
a 50 mm² cable. For a cable of 70 mm², the maximum allowed current is 118 A, which is
sufficient. Therefore, use a 3 x 70 mm² + 35 mm² cable.
If method C is used, 50 mm² is suffficient. (35 mm² for method F) => cable 3 x 50 mm² + 25
mm².
• Parallel supply cable (2 x 3 phases + PE - configuration (2)):
• I = (89 A + 10 %)/2 = (89 x 1.1)/2 = 49 A
• For a cable of 25 mm², B2 at 45 °C, the maximum current is 63 A x 0.8 = 50.4 A. So 2
parallel cables of 3 x 25 mm² + 25 mm² are sufficient.
• Install 50 A fuses on each cable instead of 100 A.