Installation method B2 according table B.52.1.
Multi-core cable in conduit on a wooden wall
Maximum allowed current in function of the ambient temperature for installation method B2
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
1.5 mm² < 15 A < 13 A < 12 A < 11 A < 9 A
2.5 mm² < 20 A < 17 A < 16 A < 14 A < 12 A
4 mm² < 27 A < 23 A < 21 A < 19 A < 16 A
6 mm² < 34 A < 30 A < 27 A < 24 A < 21 A
10 mm² < 46 A < 40 A < 36 A < 33 A < 28 A
16 mm² < 62 A < 54 A < 49 A < 44 A < 38 A
25 mm² < 80 A < 70 A < 63 A < 57 A < 49 A
35 mm² < 99 A < 86 A < 78 A < 70 A < 60 A
Installation method C according table B.52.1.
Single-core or multi-core cable on a wooden wall
Maximum allowed current in function of the ambient temperature for installation method C
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
1.5 mm² < 17 A < 15 A < 14 A < 12 A < 11 A
2.5 mm² < 24 A < 21 A < 19 A < 17 A < 15 A
4 mm² < 32 A < 28 A < 25 A < 23 A < 20 A
6 mm² < 41 A < 36 A < 32 A < 29 A < 25 A
10 mm² < 57 A < 50 A < 45 A < 40 A < 35 A
16 mm² < 76 A < 66 A < 60 A < 54 A < 46 A
25 mm² < 96 A < 84 A < 76 A < 68 A < 59 A
35 mm² < 119 A < 104 A < 94 A < 84 A < 73 A
Installation method F according table B.52.1.
Single-core cables, touching in free air
Clearance to wall not less than one cable diameter
Maximum allowed current in function of the ambient temperature for installation method F