Instruction manual
2954 2100 01 43
Notes
1) Reference conditions for engine performance to ISO 3046-1.
2) See derating diagram or consult the factory for other conditions.
3) At reference conditions unless otherwise stated.
4) Rating Definition (ISO 8528-1):
• LTP: Limited Time Power is the maximum electrical power which a generating set is capable of delivering (at variable
load), in the event of a utility power failure (for up to 500 hours per year of which a maximum of 300 hours is continuous
running). No overload is permitted on these ratings. The alternator is peak continuous rated (as defined in ISO 8528-3) at
25°C.
• PRP: Prime Power is the maximum power available during a variable power sequence, which may be run for an unlim-
ited number of hours per year, between stated maintenance intervals and under the stated ambient conditions. A 10%
overload is permitted for 1 hour in 12 hours. The permissible average power output during a 24h period shall not exceed
the stated load factor of 80%.
5) Specific mass fuel used: 0.86 kg/l.
Derating
Height
(m)
Temperature
(°C)
0 5 10 15 20 25 30 35 40 45 50
0 100 100 100 100 100 100 99 97 96 95 94
500 100 100 100 100 99 97 96 95 95 93 92
1000 98 97 97 96 96 94 93 91 90 89 89
1500 95 94 93 92 91 90 89 87 86 85 84
2000 90 89 88 87 86 84 83 82 81 80 79
2500 84 82 81 80 80 78 77 76 75 74 73
3000 78 77 76 75 74 72 71 70 69 67 66
3500 72 70 69 68 67 66 65 64 63 62 61
4000 64 63 63 61 60 59 59 57 56 54 53