Instruction book 
2920 1472 03    41 
A more detailed interpretation follows below : 
 
RSI  Tendency of the water  Action 
RSI < 3.9  Very high scale formation  Water cannot be used 
4.0 < RSI < 5.5  High boiler scale formation  Regular control and descaling 
operation necessary 
5.6 < RSI < 6.2  Slight boiler scale formation  Water treatment not necessary 
Occasional inspection recommended    
6.3 < RSI < 6.8  Neutral water  Water treatment not necessary 
Occasional inspection recommended 
6.9 < RSI < 7.5  Slight corrosion at higher 
temperature 
Water treatment not necessary 
Occasional inspection recommended 
7.6 < RSI < 9.0  Strong corrosion  Regular control necessary, use of 
corrosion inhibitor recommended 
9.1 < RSI < 11  Very strong corrosion  Regular control necessary, use of 
corrosion inhibitor required 
RSI > 11  Very strong corrosion in complete 
water system 
Water should not be used 
 
This table indicates that distilled or demineralised water should never be used, as their RSI is > 11. 
 
The RSI only indicates the equilibrium of scaling – descaling.  Cooling water showing good RSI 
conditions can still be unsuitable due to other factors. 
 
From the table above, the RSI index should be between 5.6 and 7.5; otherwise, contact a specialist. 
 
pH 
The effect of pH is already calculated in the Ryznar index, but the pH itself has some additional 
limitations: 
 
Z-units    6.8 < pH < 8.5 
 
Total dissolved solids (TDS) 
This is the sum of all ions in the water.  It can be derived from the dry residue after evaporation (but 
not including suspended solids), or it can be estimated from the electrical conductivity. 
 
In a closed system, the following limits apply : 
 
All units   TDS < 3000 mg/l  (<3800 µS/cm) 
 
For an open system, the following limits apply : 
 
Z-units    TDS < 750 mg/l   ( < 580 µS/cm) 
 
Chlorides (Cl
-
) 
Chloride ions will create pitting corrosion on stainless steel.  Their concentration should be limited: 
 
Closed cooling system:  Chlorides < 500 ppm 
Open cooling system:  Chlorides < 150 ppm 
 
However, if the water is scaling, lower limits should be used.  (See The Ryznar stability index (RSI)). 
 
Free chlorine (Cl
2
) 
Continuously, a level of 0.5 ppm should not be exceeded. 
For shock treatments, a maximum limit of 2 ppm for maximum 30 minutes/day applies. 
 
Sulphates (SO4
--
) 
Closed cooling system:  Sulphates < 400 ppm 
Open cooling systems:   Sulphates < 150 ppm