Compressors designed for a maximum ambient temperature of 40 °C (104 °F) with IE3 motors
Type FLA MCA Proposed cable
(mm²)
Maximum
cable
length (m)
Proposed
fuses (A)
(gL/gG)
Maximum
fuse (A)
(gL/gG)
Icc
ZT/ZR 110 184 202 2 X (3 X70+35) 306 2 x(3 X 160) 315 50 kA
ZT/ZR 132 219 240 2 X (3 X70+35) 306 2 x(3 X 160) 315 50 kA
ZT/ZR 145 236 259 4 X (3 X35+16) 140 2 x(3 X 200) 315 50 kA
ZT/ZR 160 285 313 4 X (3 X70+35) 233 2 x(3 X 250) 315 50 kA
ZT/ZR 200 348 383 2 X (3 X120+70) 323 2 x(3 X 250) 400 50 kA
ZT/ZR 250 428 471 4 X (3 X 95+50) 233 2 x(3 X 315) 400 50 kA
ZT/ZR 275 (7.5
bar)
469 515 4 X (3 X 95+50) 233 2 x(3 X 315) 500 50 kA
ZT/ZR 275 (8.6
and 10 bar)
524 576 4 X (3 X 120+70) 232 2 x(3 X 400) 400 50 kA
FLA and MCA based on an air-cooled full option compressor.
Icc only achieved with recommended fuses.
Compressors designed for a maximum ambient temperature of 50 °C (122 °F) with IE2 motors
Type Cables (H07V2-K) IEC 60364-5-52:
E & 4
mm
2
Fuses gL/gG
(A)
Maximum cable length
(m)
ZR/ZT 110 2 x (3x 150 + 95) 2X (3X 250) 420
ZR/ZT 132 2 x (3x 150 + 95) 2X (3X 250) 420
ZR/ZT 145 2 x (3x 150 + 95) 2X (3X 250) 420
ZR/ZT 160 2 x (3x 150 + 95) 2X (3X 250) 420
ZR/ZT 200 4 x (3x 95 + 50) 2X (3X 315) 235
ZR/ZT 250 4 x (3x 150 + 95) 2X (3X 400) 230
Compressors designed for a maximum ambient temperature of 50 °C (122 °F) with IE3 motors or
with oversized motors
Type FLA MCA Proposed cable
(mm²)
Maximum
cable
length (m)
Proposed
fuses (A)
(gL/gG)
Maximum
fuse (A)
(gL/gG)
Icc
ZT/ZR 110 203 223 2 X (3 X70+35) 306 2 x(3 X 160) 315 50 kA
ZT/ZR 132 218 240 2 X (3 X70+35) 306 2 x(3 X 160) 315 50 kA
ZT/ZR 145 218 240 2 X (3 X70+35) 306 2 x(3 X 160) 315 50 kA
ZT/ZR 160 315 347 2 X (3 X150+95) 419 2 x(3 X 250) 400 50 kA
ZT/ZR 200 389 428 4 X (3 X 95+50) 233 2 x(3 X 315) 400 50 kA
ZT/ZR 250 463 509 4 X (3 X150+95) 297 2 x(3 X 400) 400 50 kA
FLA and MCA based on an air-cooled full option compressor.