690 V - 50 Hz IEC
Compressors designed for a maximum ambient temperature of 40 °C (104 °F) with IE2 motors
Type Cables (H07V2-K) IEC 60364-5-52:
E & 4
mm
2
Fuses gL/gG
(A)
Maximum cable length
(m)
ZR/ZT 110 2 x (3x 70 + 35) 2X (3X 160) 421
ZR/ZT 132 2 x (3x 70 + 35) 2X (3X 160) 421
ZR/ZT 145 2 x (3x 120 + 70) 2X (3X 250) 449
ZR/ZT 160 2 x (3x 120 + 70) 2X (3X 250) 449
ZR/ZT 200 4 x (3x 95 + 50) 2X (3X 315) 324
ZR/ZT 250 4 x (3x 95 + 50) 2X (3X 315) 324
ZR/ZT 275 4 x (3x 95 + 50) 2X (3X 315) 324
Compressors designed for a maximum ambient temperature of 40 °C (104 °F) with IE3 motors
Type FLA MCA Proposed cable
(mm²)
Maximum
cable
length (m)
Proposed
fuses (A)
(gL/gG)
Maximum
fuse(A)
(gL/gG)
Icc
ZT/ZR 110 133 147 2 X (3 X35+16) 292 2 x(3 X 100) 315 50 kA
ZT/ZR 132 159 174 2 X (3 X50+25) 359 2 x(3 X 125) 315 50 kA
ZT/ZR 145 171 188 2 X (3 X50+25) 359 2 x(3 X 125) 315 50 kA
ZT/ZR 160 198 218 2 X (3 X70+35) 423 2 x(3 X 160) 315 50 kA
ZT/ZR 200 245 270 4 X (3 X35+16) 193 2 x(3 X 200) 315 50 kA
ZT/ZR 250 303 333 2 X (3 X120+70) 446 2 x(3 X 250) 400 50 kA
ZT/ZR 275 (7.5
bar)
327 360 2 X (3 X120+70) 446 2 x(3 X 250) 500 50 kA
ZT/ZR 275 (8.6
and 10 bar)
388 427 4 X (3 X 95+50) 322 2 x(3 X 315) 400 50 kA
FLA and MCA based on an air-cooled full option compressor.
Icc only achieved with recommended fuses.
Compressors designed for a maximum ambient temperature of 50 °C (122 °F) with IE2 motors
Type Cables (H07V2-K) IEC 60364-5-52:
E & 4
mm
2
Fuses gL/gG
(A)
Maximum cable length
(m)
ZR/ZT 110 2 x (3x 70 + 35) 2X (3X 160) 421
ZR/ZT 132 2 x (3x 70 + 35) 2X (3X 160) 421
ZR/ZT 145 2 x (3x 150 + 95) 2X (3X 250) 580
ZR/ZT 160 2 x (3x 150 + 95) 2X (3X 250) 580
ZR/ZT 200 4 x (3x 95 + 50) 2X (3X 315) 324
ZR/ZT 250 4 x (3x 95 + 50) 2X (3X 315) 324