Compressors designed for a maximum ambient temperature of 50 °C (122 °F) with IE3 motors or
with oversized motors
Type FLA MCA Proposed cable
(mm²)
Maximum
cable
length (m)
Proposed
fuses (A)
(gL/gG)
Maximum
fuse (A)
(gL/gG)
Icc
ZT/ZR 110 147 162 2 X (3 X50+25) 359 2 x(3 X 125) 315 50 kA
ZT/ZR 132 159 174 2 X (3 X50+25) 359 2 x(3 X 125) 315 50 kA
ZT/ZR 145 159 174 2 X (3 X50+25) 359 2 x(3 X 125) 315 50 kA
ZT/ZR 160 227 249 2 X (3 X70+35) 423 2 x(3 X 160) 315 50 kA
ZT/ZR 200 280 308 2 X (3 X120+70) 551 2 x(3 X 200) 400 50 kA
ZT/ZR 250 343 377 2 X (3 X150+95) 578 2 x(3 X 250) 400 50 kA
FLA and MCA based on an air-cooled full option compressor.
Icc only achieved with recommended fuses.
Compressors without starter IEC
Compressors designed for a maximum ambient temperature of 40 °C (104 °F)
Type Cables (H07V2-K) IEC 60364-5-52:
E & 4
mm
2
Fuses gL/gG
(A)
Maximum cable length
(m)
ZR/ZT 110 3x 16 + 10 3X 80 80
ZR/ZT 132 3x 16 + 10 3X 80 80
ZR/ZT 145 3x 16 + 10 3X 80 80
ZR/ZT 160 3x 16 + 10 3X 80 80
ZR/ZT 200 3x 16 + 10 3X 80 80
ZR/ZT 250 3x 16 + 10 3X 80 80
ZR/ZT 275 3x 16 + 10 3X 80 80
Compressors designed for a maximum ambient temperature of 50 °C (122 °F)
Type Cables (H07V2-K) IEC 60364-5-52:
E & 4
mm
2
Fuses gL/gG
(A)
Maximum cable
length
(m)
ZR/ZT 110 3x 25 + 16 3X 80 125
ZR/ZT 132 3x 25 + 16 3X 80 125
ZR/ZT 145 3x 25 + 16 3X 80 125
ZR/ZT 160 3x 25 + 16 3X 80 125
ZR/ZT 200 3x 25 + 16 3X 80 125
ZR/ZT 250 3x 25 + 16 3X 80 125
Instruction book