FLA and MCA based on an air-cooled full option compressor.
Icc only achieved with recommended fuses.
Compressors designed for a maximum ambient temperature of 50 °C (122 °F) with IE2 motors
Type Cables (H07V2-K) IEC 60364-5-52:
E & 4
mm
2
Fuses gL/gG
(A)
Maximum cable length
(m)
ZR/ZT 110 2 x (3x 150 + 95) 2X (3X 250) 336
ZR/ZT 132 2 x (3x 150 + 95) 2X (3X 250) 336
ZR/ZT 145 2 x (3x 150 + 95) 2X (3X 250) 336
ZR/ZT 160 4 x (3x 95 + 50) 2X (3X 315) 188
ZR/ZT 200 4 x (3x 150 + 95) 2X (3X 400) 184
ZR/ZT 250 4 x (3x 150 + 95) 2X (3X 400) 184
Compressors designed for a maximum ambient temperature of 50 °C (122 °F) with IE3 motors or
with oversized motors
Type FLA MCA Proposed cable
(mm²)
Maximum
cable
length (m)
Proposed
fuses (A)
(gL/gG)
Maximum
fuse (A)
(gL/gG)
Icc
ZT/ZR 110 248 273 4 X (3 X50+25) 165 2 x(3 X 200) 315 50 kA
ZT/ZR 132 269 296 2 X (3 X120+70) 319 2 x(3 X 200) 400 50 kA
ZT/ZR 145 269 296 2 X (3 X120+70) 319 2 x(3 X 200) 400 50 kA
ZT/ZR 160 393 432 4 X (3 X 95+50) 187 2 x(3 X 315) 400 50 kA
ZT/ZR 200 483 531 4 X (3 X 150+95) 238 2 x(3 X 400) 500 50 kA
ZT/ZR 250 582 640 4 X (3 X 150+95) 238 2 x(3 X 400) 500 50 kA
FLA and MCA based on an air-cooled full option compressor.
Icc only achieved with recommended fuses.
500 V - 50 Hz IEC
Compressors designed for a maximum ambient temperature of 40 °C (104 °F) with IE2 motors
Type Cables (H07V2-K) IEC 60364-5-52:
E & 4
mm
2
Fuses gL/gG
(A)
Maximum cable length
(m)
ZR/ZT 110 2 x (3x 120 + 70) 2X (3X 250) 325
ZR/ZT 132 2 x (3x 120 + 70) 2X (3X 250) 325
ZR/ZT 145 2 x (3x 120 + 70) 2X (3X 250) 325
ZR/ZT 160 2 x (3x 120 + 70) 2X (3X 250) 325
ZR/ZT 200 4 x (3x 95 + 50) 2X (3X 315) 235
ZR/ZT 250 4 x (3x 120 + 70) 2X (3X 400) 230
ZR/ZT 275 4 x (3x 120 + 70) 2X (3X 400) 230
Instruction book
216 2920 1815 04