SPECIFICATIONS
710-03261-00A 8 MVS SERIES
Environmental
Degree of Protection
Power Assembly ...................................................................................... IP00
Controller ............................................................................... IP54 / NEMA 12
Motor Controller Panel (optional) ........................... designed to IP54 / NEMA 12
Operating Temperature ............................................................. - 10 ˚C to + 60 ˚C
Storage Temperature ................................................................ - 25 ˚C to + 55 ˚C
Humidity ................................................................ 5% to 95% Relative Humidity
Pollution Degree ....................................................................... Pollution Degree 3
Vibration ..................................................................IEC 60068 Test Fc Sinusoidal
4 Hz to 13.2 Hz: ± 1 mm displacement
13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission
Equipment Class (EMC) ............................................................................. Class A
Conducted Radio Frequency Emission ..... 10 kHz to 150 kHz: < 120 - 69 dB µV
0.15 MHz to 0.5 MHz: < 79 dB µV
0.5 MHz to 30 MHz: < 73 dB µV
Radiated Radio Frequency Emission .... 0.15 MHz to 30 MHz: < 80-50 dB µV/m
30 MHz to 100 MHz: < 60-54 dB µV/m
100 MHz to 2000 MHz: < 54 dB µV/m
This product has been designed for Class A equipment. Use of the product in
domestic environments may cause radio interference, in which case the user may
be required to employ additional mitigation methods
.
EMC Immunity
Electrostatic Discharge ..................... 6 kV contact discharge, 8 kV air discharge
Radio Frequency Electromagnetic Field ............... 80 MHz to 1000 MHz: 10 V/m
Fast Transients 5/50 ns (main and control circuits) .................................................
2 kV line to earth, 1 kV line to line
Surges 1.2/50 µs (main and control circuits) ....2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ............ 5000 ms (at 0% nominal voltage)
(safe shutdown)
Short Circuit
Rated short-circuit current
MVSxxxx-V02-xxx .................................................................................. 68 kA
MVSxxxx-V03-xxx .................................................................................... 68 kA
MVSxxxx-V04-xxx .................................................................................. 68 kA
MVSxxxx-V06-xxx .................................................................................. XX kA
MVSxxxx-V07-xxx .................................................................................. XX kA
MVSxxxx-V11-xxx .................................................................................. XX kA
Heat Dissipation (Steady State)
Power Assembly (SCRs bypassed) ................................................. 20 W approx
Controller ........................................................................................... 10 W approx
Standards Approvals
C9 .......................................................................................... EMC requirements
UL / C-UL ..................................................................................... UL 508, UL 347
CE ........................................................................................... EMC EU Directive
Marine ...................................................................................................... pending
http://www.kontrolkalemi.com/forum/