Select parameter
3. Select parameter either:
click via the menu to parameter, or
via direct display: press and enter ID M0088.
Display indicates: Trip torque CLOSE
CLOSE or OPEN
4.
Select via Up Down :
Trip torque CLOSE
Trip torque OPEN
The black triangle indicates the current selection.
5.
Press Ok.
Display shows the set value.
The bottom row indicates: Edit Esc
6.
Press Edit.
Display indicates:
-
Specialist (4) continue with step 7
-
in bottom row Up Down Esc continue with step 11
Log on user
7.
Use Up Down to select user:
Information: Required user level: Specialist (4) or higher
The symbols have the following meanings:
-
black triangle: = current setting
-
white triangle: = selection (not saved yet)
8.
Press Ok.
Display indicates: Password 0***
9.
Enter password ( enter password).
Display shows the set value.
The bottom row indicates: Edit Esc
10.
Press Edit.
Change value
11.
Enter new value for tripping torque via Up Down .
Information: The adjustable torque range is shown in round brackets
12.
Save new value via Save.
The tripping torque is set.
13.
Back to step 4 (CLOSED or OPEN): Press Esc.
Information The following fault signals are sent if the set torque is reached in mid-travel:
Status indication S0007 Fault = Torque fault OPEN or Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
1. either by an operation command in the opposite direction.
-
For Torque fault OPEN : Operation command in direction OPEN
-
For Torque fault CLOSE : Operation command in direction CLOSE
2. or, in case the torque applied is lower than the preset tripping torque:
- via the push button RESET in selector switch position Local control
(LOCAL).