Questions and Answers

  • B
    Becky PetersonAug 16, 2025
    What to do if AUMA SQ 05.2 displays 'Fault of redundant wiring of Safe ESD input'?
    • N
      Nicholas SimmonsAug 16, 2025
      If the AUMA Controller displays 'Fault of redundant wiring of Safe ESD input', it means that both signals Safe ESDa and Safe ESDb are not simultaneously on the same level. To solve this, check the redundant control of Safe ESD signals.
  • Y
    ymclaughlinAug 19, 2025
    What does 'Actuator monitoring' mean on AUMA SQ 05.2 Controller?
    • J
      Jennifer AyersAug 20, 2025
      If the AUMA Controller shows 'Actuator monitoring', it means the actuator locked during manual operation or there is a possible defect at the actuator. Contact AUMA service.
  • E
    egordonAug 22, 2025
    What to do if AUMA Controller shows Torque fault CLOSE Torque fault OPEN?
    • Y
      yatesthomasAug 22, 2025
      If the AUMA Controller displays a torque fault in the CLOSE or OPEN directions, try executing the operation command in the opposite direction. Also, verify the torque switching setting and check for any foreign objects that might be preventing the valve from closing. There may also be problems with the valve itself.
  • D
    Dylan BeckAug 26, 2025
    What to do if AUMA SQ 05.2 Controller reports a phase fault?
    • M
      Mark HooperAug 26, 2025
      If the AUMA Controller indicates a phase fault, it means one phase of the power supply is missing, and the controls are not receiving mains voltage. To resolve this, test and connect the phases.
  • A
    andrewgreenAug 28, 2025
    Why does my AUMA Controller display 'Wrn controls temp'?
    • I
      Isabella PatelAug 28, 2025
      If your AUMA Controller displays 'Wrn controls temp,' it means the temperature inside the controls housing is too high and outside the specified range. Allow the controls to cool down. Also, check the service conditions.
  • R
    robertsmichaelAug 31, 2025
    How to fix 'Incorrect phase seq' on AUMA SQ 05.2?
    • E
      Evelyn LeeAug 31, 2025
      If the AUMA Controller displays 'Incorrect phase seq', it indicates that the phase conductors L1, L2, and L3 are connected in the wrong sequence. Correct this by exchanging two of the phases.
  • B
    Bruce NguyenSep 3, 2025
    What to do if AUMA SQ 05.2 Controller displays 'Thermal fault'?
    • R
      Robin BrownSep 3, 2025
      If the AUMA Controller displays 'Thermal fault', it means the motor protection has tripped. Allow the system to cool down and wait.
  • M
    Michael ElliottSep 6, 2025
    What does 'Wrn range act.pos.' mean on my AUMA SQ 05.2?
    • A
      Adrian House DVMSep 6, 2025
      If the AUMA Controller displays 'Wrn range act.pos.', the current position feedback signal range is outside the permissible range, or both limit switches (OPEN and CLOSED) are operated simultaneously, or there is a possible defect at actuator mechanics. Verify the reduction gearing settings within the actuator. For possible defect at the actuator contact AUMA service.
  • G
    Gary GraySep 9, 2025
    What does 'IE 24 V AC' mean on my AUMA Controller?
    • A
      Alyssa PrinceSep 9, 2025
      If the AUMA Controller displays 'IE 24 V AC', it indicates a fault in the internal 24 V AC power supply, meaning the safety-related part of the controls is without power. Check the power supply.
  • R
    ryangarrisonSep 12, 2025
    What to do if AUMA SQ 05.2 Controller has no signal in display?
    • T
      Teresa MasonSep 12, 2025
      If the AUMA Controller display shows no signal, it indicates an internal error with the SIL module electronics sub-assembly. Contact AUMA service.

AUMA SQ 05.2 Specifications

General IconGeneral
Protection classIP68
Torque range10 Nm to 50 Nm
Voltage24 V AC/DC
Ambient temperature-25°C to +70°C
CommunicationProfibus, Modbus, Foundation Fieldbus
Type of actuatorMulti-turn actuator