Emergency shutdown process:
If an emergency shutdown is required, disconnect the CIRCUIT breaker and DC switch on the AC side in
time. Otherwise, personal hazard may occur.
3.6.4 Stop the inverter
It is not necessary to shut down the inverter manually under normal circumstances, but it is necessary to
shut down the inverter for maintenance or operation. To disconnect the inverter from the AC/DC power
supply, follow the following steps. Otherwise, personal injury may occur.
Disconnect the external AC circuit breaker and prevent reconnection due to misoperation.
Turn the DC switch to position “OFF”.
Wait for about 10 minutes until the capacitor discharge is complete.
Measure the AC voltage to the ground at the AC wiring terminal and ensure that the AC output
voltage of the inverter at the AC circuit breaker is 0.
Remove the AC cable.
Remove the DC cable.
3.6.5 Dismantle the inverter
The user can dismantle the inverter according to the above electrical installation and mechanical
installation and follow the reverse steps.
3.6.6 Discarding the inverter
For inverters that will no longer be put into operation in the future, users need to properly dispose of them
by themselves.
Please strictly follow the above steps, otherwise the inverter will not work normally.
Strictly follow the preceding steps; otherwise, the inverter may fail to work properly.
The control panel, batteries, modules and other components contained in the inverter may
pollute the environment. Users need to properly dispose of them in accordance with relevant
local laws and regulations.