Digital Counter / Timer / Tach User Manual, 1st Ed.
1-800-633-0405
3-4
Signal On Delay 1 (
Sond1
)
With power applied to the CTT, the leading edge of the input
signal at START will begin the timing period setting value SV
(timing up or down based on parameter (
t modE
) or by DIP
switch 2). At the end of the timing period both outputs will
turn ON momentarily for the time set in the output pulse width
parameter (
tout1
) or will be maintained ON if the output pulse
width parameter (
tout1
) is set to 0.00. The trailing edge of the
“start” signal has no effect on the outputs or timing period.
The leading edge of a “reset” input signal at RST1 will turn
OFF the outputs and reset the timing period. The “reset” signal
minimum pulse width is set by reset pulse width parameter (
rtSr
) or DIP Switch 8.
The leading edge of a “pause” input signal at GATE will pause
the timing period after it has been started. The timing period
will continue after the trailing edge of the external switch “pause”
(Gate) signal.
When power is removed, both outputs will turn OFF and the
timing period will be reset.
Power signal
Start signal
Pause signal
Reset
Up
Down
0
0
SV
SV
Signal On Delay 1
t
t
Output
signal
Output Mode - Table 2
Switch 3 Switch 4 Output Mode
OFF OFF
Sond1
ON OFF
Sond2
OFF ON
Soffd
ON ON
Son
Dip Switch Settings - Table 1
Switch Function Off On
1 Dip switch Disabled Enabled
2 Timer mode
Counting
up
Counting
down
3
Output
mode
See Output Mode Table
- Table 2
4
5
Displayed
unit
See Display Units Table
- Table 3
6
7
8
Reset signal
pulse width
20 ms 1 ms
Display Units - Table 3
Switch 5 Switch 6 Switch 7 Display Units
OFF OFF OFF 0.01 sec.
ON OFF OFF 0.1 sec.
OFF ON OFF 1 sec.
ON ON OFF min., 0.01 sec.
OFF OFF ON min., 0.1 sec.
ON OFF ON 0.1 min.
OFF ON ON minute
ON ON ON hr., min., sec.
0V CP1
+12V RST1
RST2/
START
Start
Reset
PNP
INPUTS
0V CP1
+12V RST1
RST2/
START
Start
Reset
L-
L+
NPN
INPUTS
Outputs
Load
Load
OUT1
NPN/
SINKING
OUT2
SPDT
Load
OUT1
SPST
Load
OUT2
NPN/
SINKING
Load
+VDC
0VDC
+VDC
0VDC
0V CP1
CP2/
GATE (Pause)
+12V RST1
RST2/
START
Gate
Input
Start
Input
Reset
+VDC 0VDC
Externally Powered
(Optional)
Gate
Input(Optional)
Gate
Input(Optional)
0V CP1
+12V RST1
RST2/
START
Reset
L-
Start
Input
Gate
Input
L+
+VDC 0VDC
Externally Powered
(Optional)
Internally Powered
Internally Powered
876
131211
876
131211
Timer Wiring Examples
109
321
1514
10
15
321
876
131211
876
131211
CP2/
GATE (Pause)
CP2/
GATE (Pause)
CP2/
GATE (Pause)
CTT Timer
Signal On Delay
DIP Switch Set Up of the CTT Parameters:

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct CTT-AN-A120 and is the answer not in the manual?