DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-21
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
In the following example, Y 5 will energize whenever X1 is on, or for one CPU scan when X2
transitions from Off to On.
In the following example, Y 5 will energize whenever X1 is on, or for one CPU scan when X2
transitions from On to Off.
Aaaa
Aaaa
Y5
OUT
X1
Direct
SOFT32
X2
STR
$
CV
P
ENT
OUT
GX
3
D
SHFT
1
B
ENT
Handheld Programmer Keystrokes
5
F
OR
Q
2
C
ENT
X1
Y5
OUT
Direct
SOFT32
X2
STR
$
TMR
N
ENT
OUT
GX
3
D
SHFT
1
B
ENT
Handheld Programmer Keystrokes
5
F
OR
Q
2
C
ENT
Operand Data Type DL06 Range
A
aaa
Inputs X 0–777
Outputs Y 0–777
Control Relays C 0–1777
Stage S 0–1777
Timer T 0–377
Counter CT 0–177
DS Implied
HPP Used
DS Implied
HPP Used
DirectSOFT
DirectSOFT
Or Positive Differential (ORPD)
The Or Positive Differential instruction logically ors a
contact in parallel with another contact in a rung. The
status of the contact will be open until the associated
image register point makes an Off-to-On transition,
closing it for one CPU scan. Thereafter, it remains
open until another Off-to-On transition.
Or Negative Differential (ORND)
The Or Negative Differential instruction logically ors a
contact in parallel with another contact in a rung. The
status of the contact will be open until the associated
image register point makes an On-to-Off transition,
closing it for one CPU scan. Thereafter, it remains
open until another On-to-Off transition.