DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-76
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
In the following example when X1 is on, the binary value in the accumulator will be ORed
with the binary value in the first level of the stack. The result resides in the accumulator.
ORS
LDD
V1400
0010100001111010
01101010011110100000010000000000
V1400
287A
0111011001111111
0101010001111110
15 14 13 12 11 10 9876543210
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 1631 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Acc.
Ac c
.
Acc.
V1500
6A7 A
V1401
547E
V1501
767F
0101010001111110 0010100001111010
0110101000111000001101 100100011
1
DirectSOFT32
X1
Load the value in V1400 and
V1401 in the accumulator
ORS
OR the value in the
accumulator with the value
in the first level of the
accumulator stack
OUTD
V1500
36476A38
OR (top of stack)
Copy the value in the
accumulator to V1500 and
V1501
Handheld Programmer Keystrokes
1
B
ENT
1
B
4
E
0
A
0
A
ENT
STR
$
SHFT
ANDST
L
3
D
OUT
GX
SHFT
3
D
1
B
5
F
0
A
0
A
ENT
3
D
OR
Q
SHFT
RST
S
ENT
Discrete Bit Flags Description
SP63 ON if the result in the accumulator is zero.
SP70 ON if the result in the accumulator is negative.
DS Used
HPP Used
DirectSOFT
Or with Stack (ORS)
The ORS instruction is a 32-bit instruction that logically ORs the
value in the accumulator with the first level of the accumulator
stack. The result resides in the accumulator. The value in the
first level of the accumulator stack is removed from the stack and
all values are moved up one level. Discrete status flags indicate
if the result of the ORS is zero or a negative number (the most
significant bit is on).