GS1 Series AC Drive User Manual
4–41
Chapter 4: AC Drive Parameters
Over-current Stall Prevention during Acceleration Mem Addr 060AH(41547)
Range: 20 to 200% Default setting: 150
A setting of 100% is equal to the Rated Output Current of the drive.
• Under certain conditions, the AC drive output current may increase abruptly,
and exceed the value specified by 6-10 This is commonly caused by rapid
acceleration or excessive load on the motor. When this function is enabled, the
AC drive will stop accelerating and maintain a constant output frequency. The
AC drive will only resume acceleration when the current drops below the
maximum value.
Over-current Stall Prevention during Operation Mem Addr: 060BH(41548)
Range: 20 to 200% Default Setting: 150
• During steady-state operation with motor load rapidly increasing, the AC drive
output current may exceed the limit specified in 6-11. When this occurs, the
output frequency will decrease to maintain a constant motor speed. The drive
will accelerate to the steady-state output frequency only when the output
current drops below the level specified by 6-11.
6-11
6-10