7
By repeatedly pressing the set button you can scroll to the part of the
set up programme you require.
You may receive an ERR3 / ERR4 message, if this happens allow the
cam shafts to turn for a few moments and this code should disappear. If
the cam does not move check that the Cam Shafts are fitted correctly
and that the optical sensors are in position.
Set Time.
Press the set button. The TIME should now be flashing, use the up and
down arrows to set the correct time of day (24hrs format). Once the
correct time has been selected, press the set button to confirm. The
following will then be displayed.
Set Day of the Week.
Press the set button to display the screen shown. The display will flash,
use the up and down buttons to advance the arrow to underneath the
correct day. Once under the correct day press the set button to confirm.
The following will then be displayed.
Time when system Regenerates.
This normally defaults to 2.00am but can easily be changed to a more
suitable time if required by pressing the square set button to start the
display flashing, adjusting the time using the up and down arrows then
press the square set button to confirm. The following will then be
displayed.
Calendar Override Days.
The system should have this pre-programmed to a suggested number
of days but this may need altering to suit your needs. This function
allows the filter bed to backwash regardless of usage; this is to ensure
that the filter bed remains fresh.
Press the set button to start the display flashing then alter the figure
using the up and down arrows, then press the set button to confirm the
setting.
Hardness Setting
The hardness setting will need to be set on site, the setting is in ppm.
Press the set button to start the display flashing and adjust the
hardness value up or down using the up and down arrows, when the
correct figure is displayed press the square button to set.
Capacity.
System capacity is displayed in kilograms of hardness removed before
regeneration is necessary. This should be factory set but should it
require setting you need to press the set button to start the display
flashing, then adjust the figure using the up and down arrows and press
the set button to confirm the figure. (see section 5.1)