EasyManua.ls Logo

Autronica Autroprime BS-200 - Panel Inputs and Outputs; Main Terminal Block J1

Autronica Autroprime BS-200
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panel Inputs and Outputs
System Description, Autroprime Interactive Fire Detection System, 116-P-APRIME-SYSTEMD/XGB 2007-10-10,
Autronica Fire and Security AS
Page 21
4. Panel Inputs and Outputs
4.1.1 Main Terminal Block J1
Det.Loop2 in - 32
Det.Loop2 in + 31
Det.Loop2 out - 30
Det.Loop2 out + 29
For connection of
Max 127 detectors/loop units
Det.Loop1 in - 28
Det.Loop1 in + 27
Det.Loop1 out - 26
Det.Loop1 out + 25
For connection of
Max 127 detectors/loop units
Rel.Outp.2 NC 24
Rel.Outp.2 NO 23
Rel.Outp.2 Com 22
Default configured as
Fault Warning Routing Equipment.(FWRE)
Potential free changeover contact.
Non-monitored. Max.30VDC/1A
Rel.Outp.1 NC 21
Rel.Outp.1 NO 20
Rel.Outp.1 Com 19
Default configured as
Fire Alarm Routing Equipment.(FARE)
Potential free changeover contact.
Non-monitored. Max. 30VDC/1A
Aux1 +24V out 18
Supply voltage for loads connected to
Open collector outputs 1 and 2. Max.1A
Open Collector
Output 2
17
User configurable Open collector output.
Non-monitored
Switches to 0V at activation. Max.0,5A
Open Collector
Output 1
16
User configurable Open collector output.
Non-monitored
Switches to 0V at activation. Max.0,5A
Mon.Outp.2 0V 15
Mon.Outp.2 +24V 14
Mon.Outp.1 0V 13
Mon.Outp.1 +24V 12
Default configured as Fire Alarm Device
Output. Monitored for short and open circuit. 2kohm end resistor. Max 500mA
Mon.Inp.0V 11 0V reference for Monitored Inputs 1 & 2
Mon.Inp. 2 10
User configurable input. Monitored for open and short circuit.2k resistor to 0V.
Activates at 910 ohm to 0V
Mon.Inp. 1 9
User configurable input. Monitored for open and short circuit.2k resistor to 0V.
Activates at 910 ohm to 0V
Aux2 0V out 8
Aux2+24V out 7
Power to panel bus.
Max 1A (Fuse F4)
Aux1 0V out 6
Aux1+24V out 5
Power to panel bus.
Max 1A (Fuse F1)
(includes output 18)
Charger 0V 4
Charger +24V 3
For connection of internal charger
Battery - 2
Battery + 1
For connection of standby battery
Fuse F2, 5A

Table of Contents

Related product manuals