5.2 Establish AutroFieldBus communication
AutroFieldBus communication is up running on a panel already in commissioning mode. On a
running AutroFieldBus it is possible to remotely access PowerLoop drivers from another
PowerLoop driver with a PC connected. Use command #LoginX, where X = address on AFB
(exclude +40 settings and system number). This is useful to fetch crosstalk statistics and PL_stats
(see chapter 5.4.2 Discover crosstalk). In addition, you may fetch the topology. Avoid using other
commands as this will cause too high load on the PowerLoop driver you are connected to with a
PC.
Recommended procedure:
1. Start log to file (easy to read when finished)
2. #LoginX
3. #? (to have reference to loop driver in log file)
4. #Printcross
5. #PL_stat
6. #prntop (list existing topology as well as saved)
7. #LogoutX (important)