Service Commands
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 108
Step Actions to be taken Display Indication
8
To accept the selected Alarm Zone and activate
the test, press twice on
A test signal will be sent to all Fire Alarm Devices
within the selected Alarm Zone.
14.3.2.3 Manual Test ON- Fire Alarm Routing Equipment (FARE)
The test is similar to the test for Fire Alarm Devices (FAD) and it
requires Access Level 3 (password restricted). For detailed
description, refer to 14.3.2.2.
When the test is initiated, a test signal will be sent to all Fire Alarm
Routing Equipment (FARE) within the Operation Zone (if there are
several Operation Zones, the signal will be sent to FARE in all
Operation Zones). The duration of the signal and the interval between
each signal are configurable (normally 1 second ON and 30 seconds
OFF).
The test signal is given the lowest priority. In the event of an alarm,
the alarm signal will thus override the test signal.
14.3.2.4 Manual Test ON- Fault Warning Routing Equipment (FWRE)
The test is similar to the test for Fire Alarm Devices (FAD) and it
requires Access Level 3 (password restricted). For detailed
description, refer to 14.3.2.2.
When the test is initiated, a test signal will be sent to all Fault Warning
Routing Equipment (FWRE) within the Operation Zone (if there are
several Operation Zones, the signal will be sent to FARE in all
Operation Zones). The duration of the signal and the interval between
each signal are configurable (normally 1 second ON and 30 seconds
OFF).
The test signal is given the lowest priority. In the event of an alarm,
the alarm signal will thus override the test signal.
SERVICE
19:23
MANUAL TEST ON
1 FIRE ALARM DEVICES
2 FIRE PROTECTION EQUIPMENT
3 FIRE WARNING ROUTING EQUIPMENT
4 OTHER OUTPUTS
SERVICE
19:23
MANUAL TEST ON
1 FIRE ALARM DEVICES
2 FIRE PROTECTION EQUIPMENT
3 FIRE WARNING ROUTING EQUIPMENT
4 OTHER OUTPUTS