Service Commands
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 128
Step Actions to be taken Display Indication
To select SV-Fault, press 1
Comments: In this example one detector has been reported
with SV-Fault.
Action Digit 4: Print will appear only if a printer is
connected.
Comments: The point information includes the point’s
tagname followed by the Loop Sequence
Number (LSI), the name of the zone, the loop
and its corresponding loop driver module’s
physical position in the module stack inside the
cabinet (counted from bottom to top above the
BSL-310 board), the Fire Alarm Control Panel’s
name and its address, and finally the exact time
and date when SelfVerify failed for this point.