Appendix
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 156
Action Digits
Action Digit When action is available Used to…..
PROLONG
DELAY
Delayed Action detection zone having
entered the fire alarm condition and is
in its T1 period. The T1 delay period
is started when a Fire Alarm signal
from a point is received.
(Not included in SOLAS version).
• terminate the T1 delay period
and start the T2 delay period.
BLOCK
As PROLONG DELAY above.
Used in a SOLAS Action detection
zone.
The T1 delay period is started when a
Fire Alarm signal from a point is
received.
• terminate the T1 delay period
and block the alarm for an
indefinite period of time.