In the Event of a Fire Alarm
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 49
Step Actions to be taken Display Indication Audible Indication
The point(s) still in alarm will be
shown on the display.
If no actions are taken, the
points still signalling alarm will
automatically be reactivated
after a predefined timeout.
If you want to disable the
point(s) - for example, a manual
call-point -still signalling alarm,
go to step 11. The points can
also be reactivated (step 12) at
any time after the disablement
(ALARMDISABLE) has taken
place.
To disable all points still
signalling alarm, press
Comments: The red Fire Brig. Signalled indicator goes off.
The yellow Function Disabled indicator is lit.
All point(s) still signalling alarm are disabled. To reactivate the point(s), you
have to press Action Digit 3 (REACTIVATE).
To reactivate the
point(s), press Action
Digit 3.
The point(s) will again
signal alarm.
The internal buzzer on
the operator panel is
turned on.
Comments: The yellow Function Disabled indicator goes off.
The red FIRE indicator starts to blink.
The red Fire Brig. Signalled indicator is lit.
To reset the system,
repeat step 9 and 10.
(Press the red Silence
Alarms button and the
green Reset button).
Comments: If there are no points signalling a fire alarm, the system is reset.
The red FIRE indicator goes off.
The red Fire Brig. Signalled indicator goes off.
The panel enters its idle state.