4.3 Operating principle
When the rate of disinfectant is insufficient: redox value < Value records (30 mV of mini gap) then:
- The electrolyser with salt is fed
- The device shows the redox value there mV
When the rate of disinfectant is sufficient : redox value ≥ Value records then:
- The electrolyser with salt is not fed
For example, for a value record 640 mV:
- Measured value > 640 mV: STOP of the salt water chlorinator
- Measured value 610 mV: Switch on the salt water chlorinator
4.4 Manual supply of the electrolyser with salt
4.5 Adjustment of the set point
5.0 ALARMS « ALR »
The alarm bustles when the value redox is lower than 100 mV or superior to 900 mV: the device does not
feed the electrolyser with salt.
The screen alternates between “ALr
and “the Redox value .
When the device is on standby state (display on
« OFF »), press ON/OFF during 3 second. It starts the
water salt chlorinator.
To change the value of the set point, hold the SET key and
press CAL by pulse. Each pulse changes the Redox value of
10mV between 350 and 850mV.
When you press the SET button, the
value of the set point is displayed.