30 Level II Programming
Rev C
Adjusting the Cycle Times
The following cycle times are adjustable.
Refill time does not appear as this cycle time is determined by the salt
setting.
The controller calculates the Slow Rinse default time based on injector
type, system size and salt dosage. The cycle times can be adjusted for
custom applications. Please contact your AvantaPure Water Treatment
Professional before attempting to adjust the Slow Rinse time.
•Viewing Operation Type
This parameter displays the controller type and is preset at the
factory: 269 Counter current conditioner.
Setting the Service Interval
The service interval feature is an option that will allow the installer to
program the unit to ask for maintenance after a programmed
duration. The feature is programmed from 0 (zero) to 99 months. When
the programmed length of time has been reached the words "CALL
DEALER FOR SERVICE" will appear in the banner display to signal the
end user that regular maintenance may be required. If it is set to 0
(zero) the function is disabled. If you wish to enable this function
program the desired service interval duration.
Setting the Chlorine Generator/Salt Check (conditioner only)
The controller has the capability to produce a low level of chlorine
during the brine draw stage of regeneration. It can also sense if there
is any brine present during the time when brine draw is occurring. This
parameter can be adjusted to the following:
0 = Chlorine Generator with Salt Check disabled
1 = Salt Check only
2 = Chlorine Generator with Salt Check enabled
A chlorine generator refill control/cable kit, P/N 3001760, must be
installed for this function to work properly. After it is installed, select
the desired parameter and push SET to accept the selection.
Cycle Range
Slow Rinse 1 to 125 minutes
Backwash 1 to 50 minutes
Fast Rinse 1 to 30 minutes