EasyManua.ls Logo

Axis use-IP A1610 - Page 23

Axis use-IP A1610
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AXISA1610NetworkDoorController
Specifications
Important
Whenthereaderispoweredbythecontroller,thequaliedcablelengthisupto150m(500ft).
Whenthereaderisnotpoweredbythecontroller,thequaliedcablelengthforreaderdataisupto150m(500ft)
ifthefollowingcablerequirementismet:AWG20-16.
Supervisedinputs
Tousesupervisedinputs,installendoflineresistorsaccordingtothediagrambelow.
iInput
ii
0VDC(-)
UL:SupervisedinputswerenotevaluatedbyULforburglaryuse.OnlydoormonitorandREXsupportsupervisionwithendof
lineresistors.
Note
Itisrecommendedtousetwistedandshieldedcables.Connectshieldingto0VDC.
Doorconnector
Two4-pinterminalblocksfordoormonitoringdevices(digitalinput).
Onlydoormonitorsupportssupervisionwithendoflineresistors.Iftheconnectionisinterrupted,analarmistriggered.Touse
supervisedinputs,installendoflineresistors.Usetheconnectiondiagramforsupervisedinputs.Seepage23.
FunctionPinNotes
Specications
DCground
1,3
0VDC
Input
2,4
Forcommunicatingwithdoormonitor.
DigitalinputorSupervisedinputConnectto
pin1or3respectivelytoactivate,orleaveoating
(unconnected)todeactivate.
0tomax30VDC
Important
Thequaliedcablelengthisupto30m(98.4ft)ifthefollowingcablerequirementismet:AWG24.
Relayconnector
Two4-pinterminalblocksforformCrelaysthatcanbeused,forexample,tocontrolalockoraninterfacetoagate.