AXISA1610NetworkDoorController
Specifications
FunctionPinNotes
Specications
DCground
1
0VDC
DCoutput
2
Canbeusedtopowerauxiliaryequipment.
Note:Thispincanonlybeusedaspoweroutandonthesecureside
sinceitsharespowerwiththerelays.
12VDC
Maxload=50mAforeach
I/O
DigitalinputorSupervisedinputConnecttopin1toactivate,or
leaveoating(unconnected)todeactivate.Tousesupervisedinput,
installend-of-lineresistors.Seeconnectiondiagramforinformation
abouthowtoconnecttheresistors.
0tomax30VDC
Congurable
(InputorOutput)
3–6
DigitaloutputInternallyconnectedtopin1(DCground)when
active,andoating(unconnected)wheninactive.Ifusedwithan
inductiveload,e.g.,arelay,connectadiodeinparallelwiththe
load,toprotectagainstvoltagetransients.EachI/Oiscapableof
driving12VDC,50mA(max)externalload,ifinternal12VDC
output(pin2)isused.Inthecaseofusingopendrainconnections
incombinationwithanexternalpowersupply,thentheI/Oscan
manageDCsupplyof0–30VDC,100mA.
0tomax30VDC,opendrain,
100mA
1
DCground
2
DCoutput12V,max50mA
3
I/Oconguredassupervisedinput
4
I/Oconguredasoutput
5
CongurableI/O
6
CongurableI/O
Externalconnector
4-pinterminalblockforexternaldevices,forexampleglassbreakorredetectors.
UL:TheconnectorhasnotbeenevaluatedbyULforburglar/realarmuse.
FunctionPinNotes
Specications
DCground
1,3
0VDC
25