Wiring
CAUTION
Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.
All wiring must comply with applicable codes and ordinances.
Before wiring, be sure to turn off the power to the product.
Failure to do so might cause electric shock.
To connect the wires to the screw terminals, use crimp terminal lugs with insulation.
Failure to do so might cause fire or device failure due to short circuit.
Model TTY6023Z2000 adopts lead wire connection and the rest of the models adopt terminal connection.
Precautions for wiring
● Use M4 crimp terminals to connect wires to the Neostat screw terminals. (Tightening torque: 78.5 Nꞏcm)
● For connecting wires from the load, use 1.25 mm
2
or greater stranded annealed copper wires with insulation.
● For splicing lead wires (from the load and from Neostat), use crimp sleeves with insulation.
● Correctly connect the wires from the load to Neostat.
● Make sure that all the wires are tightly connected.
Wiring diagram
Neostat (Model TY9001Z2000(-1))
ACTIVAL or
Control Motor
Transformer
Temp rise
Heating
Cooling
Switch
Figure 14. Wiring diagram: Model TY9001Z2000(-1)
Temp rise
Cooling equip
Heating equip
Figure 10. Wiring diagram: Model TY6000Z2000(-1)
Neostat (Model TY6000Z2000(-1))
Temp
rise
Switch
Heating
Cooling
Cooling
(/heating) equip
Figure 11. Wiring diagram: Model TY6001Z2000(-1)
Not used
Neostat (Model TY6001Z2000(-1))
Cooling Heating
First
step
Second
step
Second
step
First
step
Temp rise
Temp drop
Temp rise
Temp drop
Cooling equip
Heating equip
Cooling equip
Heating equip
R
B
G
P
W
Bk
Lead wire color
R: Red, B: Blue, G: Gray P: Pink, W: White, Bk: Black
Figure 12. Wiring diagram: Model TTY6023Z2000(-1)
Neostat (Model TTY6023Z2000(-1))
Transformer
ACTIVAL or
Control Motor
Temp rise
Figure 13. Wiring diagram: Model TY9000Z2000(-1)
Neostat (Model TY9000Z2000(-1))
Humidity rise
Humidifier
Dehumidifier
Figure 15. Wiring diagram: Model HY6000Z2000(-1)
Neostat (Model HY6000Z2000(-1))