EasyManua.ls Logo

Bacharach INJECTOR CALIBRATOR CD3 - Page 23

Bacharach INJECTOR CALIBRATOR CD3
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instructions 67-9319 Bacharach, Inc. Page 2-5
INJECTOR CALIBRATOR CD3 INSTALLATION
Figure 2-12. Initial Checks - Air Pressure
Figure 2-13. Initial Checks - Calibration Fluid
Figure 2-14. Initial Checks - Cambox Oil
CONDITION YES NO
_______________________________________________
3. The air line from the shop air _____ _____
supply is connected to the AIR
inlet at the back of the calibrator.
4. The cold water line is connected_____ _____
to the WATER IN port.
5. The drain line is connected to _____ _____
the WATER OUT port.
NOTE: Do not connect any valve,
shutoff, or other restriction in
the drain line.
6. Inlet Air Pressure Regulator _____ _____
gauge. (Inside lower rear
panel) indicates 90 ± 5 psi.
Secondary Air Pressure
Regulator must read 60 psi
(4.1 bar) +5 -0 psi. Reset if
necessary.
NOTE: Air pressure regulators
were set at the factory.
7. Both drain valves are closed on_____ _____
the calibration fluid reservoir.
8. The calibration fluid reservoir _____ _____
is filled to the “F” mark on the
dipstick. Use Calibration Fluid
P.N. 67-5598 (SAE J967).
9. The cambox is filled with oil _____ _____
to 3-3/4 inch from the top of
cam box. If additional oil is
required, use SAE 30W motor
oil (non-detergent).
*If electrical power does not correspond to the data
on the nameplate, consult the Bacharach factory.
(Checklist continued on next page)
Secondary
7 Reservoir
Drain Valves
6 Air Pressure
Re
ulator Gau
es
Primary
8 D i p s t i c k
9 C a m b o x O i l

Table of Contents

Related product manuals