EasyManua.ls Logo

Bacharach MultiZone - System Data Register 0 X0010 (16 Dec) (R;W, 54 Bytes); Status Register 0 X001 (17 Dec) (R;W, 10 Bytes)

Bacharach MultiZone
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multi-Zone Gas Monitors
58 P/N: 3015-5074 Rev 11
B.3.7. System Data Register 0x0010 (16 Dec) (R/W, 54 Bytes)
Variable Type Length Description
Type
UI
2 bytes
Indicates EEPROM has been initialized if value = 300 DO NOT MODIFY
REV
Float
4 bytes
Firmware Rev Level DO NOT MODIFY
UNUSED
UI
2 bytes
Firmware Serial Number DO NOT MODIFY
Node UC 1 byte
Network Slave Node # (valid values are 1-15). The default is that
indicated by the Node DIP Switch on main board.
Location
C
13 bytes
Array defining text name of unit
Stop_Bits C 1 byte
Number of stop bits used in the MZ data stream. Default = 1. Other
available value is 2
Aud_Alarm UC 1 byte
Sounds internal board buzzer on condition; 0 = no buzzer; 1= Alarm;
2=Fault; 3=Leak; 4=Spill; 5=Evacuate; 6=Monitor Off line (DEFAULT =
0)
Alarm_Ack_
Mode
UC 1 byte
Defines Alarm Operation. Manual Acknowledge = 0; Auto Acknowledge
= 1 (DEFAULT = 0)
Num_Zones UC 1 byte
Number of install zones (Value initialized during auto detect during
Power On Self Test).
UNUSED TIM 13 bytes UNUSED
Rezero_Mode UC 1 byte
Defines re-zero mode. Auto Re-zero = 0; Re-zero every zone = 1
(DEFAULT = 0)
Hold_Time
UI
2 byte
Length of zone hold interval in minutes (DEFAULT = 15 minutes)
UNUSED UC 1 byte
Minim um detection limit (in PPM).
Concentrations less than or equal this
value will read as 0 PPM (DEFAULT = 0 PPM)
Avg_Size UC 1 byte
Size of running average used in computing PPM value. DO NOT
MODIFY.
Loop2_factor
Float
4 bytes
Defines PPM current loop output. (DEFAULT = 0.16 mA/PPM)
Serv_Mode_TO UI 2 bytes Service Mode Timeout value (in minutes). (DEFAULT = 60 MINUTES)
RS485_BAUD UI 2 bytes
BAUD RATE for RS-485 connection (between RD and MZ monitor or
MODBUS master and MZ depending on the Network topology).
Default=9 (19.2K); other values are 8=9600, 7=4800
Mode
UI
2 bytes
UNUSED
B.3.8. Status Register 0x011 (17 Dec) (R/W, 10 Byte s)
Variable Type Length Description
Mode UC 1 byte
Defines Operating Mode of MZ. 0 = normal Mode; 1 = Zone_Hold Mode; 2
= Diagnostic Mode; 3 = Service mode. DO NOT MODIFY (use zone hold
register or service mode register to change this parameter)
State UC 1 byte
Defines MZ Current State. 0 = Idle; 1 = Sampling; 2 = Zeroing; 3 = Warm
Up, 4 = Pressure Check DO NOT MODIFY
Measuring UC 1 byte
Value = 1 if unit is acquiring detector signal for running avg. DO NOT
MODIFY
Active_Zone UC 1 byte Current Zone being checked. 0=zone 1, 1=zone 2, etc.
Ma x _ Alarm UC 1 byte Indicates highest non-acknowledged alarm level DO NOT MODIFY
Alarm_Count UC 1 byte Number of alarms that are currently active. DO NOT MODIFY
UNUSED UC 1 byte UNUSED
Loop_Card UC 1 byte Value = 1 if 4-20 mA card has been detected. DO NOT MODIFY
Fault UI 2 bytes
Fault Flag Structure uses bitwise access to 16 bit word as defined in the
table below.

Table of Contents

Related product manuals