Installation & Operation Manual
Terminal 07-08 analog output (SETUP 7)
An isolated 4…20 mA signal proportional to the flow rate is available for the ER-420-DC and ER-420-AC.
When the output is disabled, a 3.5mA signal will be generated on these terminals.
Maximum driving capacity is 1000 Ohm @ 30V DC.
Terminal 09-11 flowmeter input
Two basic types of flowmeter signals can be connected to the unit: passive or active pulse.
The screen of the signal wire must be connected to the common ground terminal 9 (unless earthed at the sensor itself).
The maximum input frequency is approximately 10 kHz (depending on the type of signal). The input signal type has to be
selected with the correct SETUP-function (see "Details of Setup Functions" on page 14).
Pulse-signal NPN / NPN-LP
The ER-420 is suitable for use with flowmeters which have a NPN output signal. For reliable pulse detection, the pulse
amplitude has to go below 1.2V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input
frequency (see "Details of Setup Functions" on page 14).