D10 Expert™ Discrete Output with Bargraph Display
Push Button
0.04 seconds ≤ “Click” ≤ 0.8 seconds
Remote Line
0.04 seconds ≤ T ≤ 0.8 seconds
Result
Access
SET Mode
• Press and hold Static push
button > 2 seconds
• Single-pulse remote line
Power LED: OFF
Output LED:
ON (push button)
OFF (remote line)
Static LEDs:
LO & DO alternately
flashing
SET Sensing Condition
• Present sensing condition
• Five-click Static push button
• Present sensing condition
• Five-pulse remote line
Threshold Condition Accepted
Power LED: ON
Output LED:
ON (push button)
OFF (remote line)
Bargraph:
4 indicators flash
together
Sensor returns to RUN mode with new settings
Threshold Condition Unacceptable
Power LED: ON
Output LED:
ON (push button)
OFF (remote line)
Bargraph:
#1, 3, 5, 7 flash to show
failure
Sensor returns to “SET Sensing Condition.”
TT T
1x
2x
3x
4x
5x
6x
7x
T
0.8 seconds
> 2 seconds
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T T T
B_028256
TT T
1x
2x
3x
4x
5x
6x
7x
T
0.8 seconds
> 2 seconds
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T T T
B_028256
Single-Point Dark SET
• Sets a threshold 6.25% above the taught condition.
• Any condition lighter than the threshold condition causes the output to change state.
• Threshold position is adjustable using the “+” and “-” buttons (Manual Adjust).
• Recommended for applications where only one condition is known, for example a stable
dark background with varying lighter targets.
A single sensing condition is presented, and the sensor positions a threshold 6.25%
above the taught condition. When a condition lighter than the threshold is sensed, the
output either turns ON or OFF, depending on the Light/Dark Operate setting (see SETUP
mode, page 8).
Dark SET and Light/Dark Operate Selection
In Light Operate mode, Dark SET teaches the Output OFF condition. In Dark Operate
mode, Dark SET teaches the Output ON condition.
Figure 6. Single-Point Dark SET (Light
Operate shown)
Sensor positions
window thresholds
≈10%
from the
presented condition
Sensor positions
threshold between
taught conditions
Threshold position
adjusted by
Manual Adjust
Threshold position
adjusted by
Manual Adjust
Sensor positions
threshold between
taught conditions
Sensor positions
threshold 6.25% below
the presented condition
Sensor positions
threshold 6.25% above
the presented condition
Darkest
(no signal)
Darkest
(no signal)
Darkest
(no signal)
Most Light
(saturated
signal)
Most Light
(saturated
signal)
Darkest
(no signal)
Most Light
(saturated
signal)
Most Light
(saturated
signal)
Condition
Presented
Sensing window size
adjusted by
Manual Adjust
Output OFF Output OFF
Output OFF
Output ON
Output ON
Darkest Taught
Condition
Lightest Taught
Condition
Position
adjusted by
Manual Adjust
Output OFF Output ON
Condition
Presented
Output OFF Output ON
Condition
Presented
Darkest
(no signal)
Most Light
(saturated
signal)
Output OFF Output ON
2nd Taught
Condition
1st Taught
Condition
Position
adjusted by
Manual Adjust
dynamic
static
8
4
6
5
3
2
1
7
DO
LO
HS
dynamic
static
8
4
6
5
3
2
1
7
DO
LO
HS
dynamic
static
8
4
6
5
3
2
1
7
DO
LO
HS
dynamic
static
8
4
6
5
3
2
1
7
DO
LO
HS
or
or
or
dynamic
static
8
4
6
5
3
2
1
7
DO
LO
HS
dynamic
static
8
4
6
5
3
2
1
7
DO
LO
HS