Units Description Definition
7 Temp °F Fahrenheit, high resolution. Analog input for temperature devices such as thermocouples, RTD,
and thermistors. In high resolution mode, temperature = (Modbus register value) ÷ 20.
LCD: 0000.0F
8 Temp °C (Low
Res)
Celsuis, low resolution. To measure a greater temperature range, use the low resolution unit. In
low resolution mode, temperature = (Modbus register value) ÷ 2.
LCD: 0000.0C
9 Temp °F (Low
Res)
Fahrenheit, low resolution. To measure a greater temperature range, use the low resolution
unit. In low resolution mode, temperature = (Modbus register value) ÷ 2.
LCD: 0000.0F
10 Asynchronous
Counter, 32-
bit
The 32-bit counter value records counts up to 4.29 billion.
LCD: 0000 0000
11 Asynchronous
Counter, 16-
bit
The 16-bit counter value records counts up to 65535.
LCD: 0000
5.9 Output Units
Units Description Definition
0 Raw Displays the raw A/D conversion data with data ranges from 0 to 65535. This units type is typi-
cally used only for factory calibration.
LCD: Raw A/D hex value
1 4 to 20 mA Analog unit. Modbus register contents are scaled such that 0 represents 4 mA and 65535 repre-
sents 20 mA.
LCD: 4.00mA–20.00mA
2 0 to 20 mA Default analog input unit. Modbus register contents are scaled such that 0 represents 0 mA and
65535 represents 20 mA.
LCD: 0.00mA–20.00mA
3 Discrete (ON/
OFF)
Default discrete unit.
LCD: ON/OFF
4 0 to 10V
(Volts)
Analog unit using 0 to 10V instead of current. Modbus register contents are scaled such that 0
represents 0V and 65535 represents 10V.
LCD: 0.00V–10.00V
5 Signed Ana-
log, 0 to 10V
For a signed value, such as temperature, that is to be converted to a voltage out value. Use
null to set the start point and span to define the range. The null value is the starting tempera-
ture to be associated with 0V. The span is the entire temperature range that is to be associated
with 0 to 10V.
LCD: 0.00V–10.00V
SureCross DX80 and Performance DX80 Product Manual
48 www.bannerengineering.com - tel: 763-544-3164 Rev. J