RF Link Time-Out and Recovery
The SureCross™ DX80 wireless devices employ a deterministic link time-out method to address RF link interruption or failure. As soon as
a speci c Node/Gateway RF link fails, all pertinent wired outputs are de-energized until the link is recovered (see component data sheet for
more information.) Through this process, users of Banner wireless networks can be assured that disruptions in the communications link will
result in predictable system behavior.
The link time-out feature uses a fully-acknowledged polling method to determine the RF link status of each Node on the network. If after
a speci ed number of sequential polling cycles the Node does not acknowledge a message, the Gateway considers the link with the
Node timed out. LCD displays on both the Node and Gateway show *ERROR. Following a time-out, the Node de-energizes outputs and
the Gateway sets all outputs linked to the Node in question to a de-energized state. Inputs from the Nodes are mapped to outputs on the
Gateway and are suspended during a link timeout.
Once a link has failed, the Gateway must receive a speci ed number of good RF communications packets from the Node in question before
the link is reinstated. Outputs are restored to current values when the link is recovered.
For information regarding Host-connected systems and link time-out and recover, please refer to Banners DX80 and Modbus Guide.
Link between Gateway and Node 1 timed out.
Link between Gateway and Node 1 recovered.