9252000995 Rev G BE1-50/51B-218/-228 General Information 1-9
Radio Frequency Interference (RFI)
Field-tested using a 5-watt, hand-held transceiver operating at random frequencies centered around 144
MHz and 440 MHz, with the antenna located 6 inches from the relay in both horizontal and vertical
planes.
Vibration
Withstands 2 G in each of three mutually perpendicular planes swept over the range of 10 to 500 Hz for a
total of 6 sweeps, 15 minutes each sweep.
Shock
Withstands 15 G in each of three mutually perpendicular planes.
Environment
Operating Temperature: –40°C to 70°C (–40°F to158°F)
Storage Temperature: –50°C to 70°C (–58°F to 158°F).
Agency Recognition
GOST-R Certification
GOST-R certified No. POCC US.ME05.B03391; complies with the relevant standards of Gosstandart of
Russia. Issued by accredited certification body POCC RU.0001.11ME05.
Physical
Case Size: S1 (Refer to Section 4, Installation for case dimensions.)
Weight: 6.4 lb (2.77 kg)