1-4 BE1-50 General Information 9171000990 Rev E
Table 1-1. Current Ratings and Sensing Burdens
Power
Supply
Sensing Range
Designation
Maximum Rating 50 or 60 Hz
Current
For
Phase
For
Neutral
Actual Sensing
Range
K ∗
1
Second
Continuous
Burden Per
Input
1 D 0.25 - 0.5 A 144 12.0 A 0.75 A 8.5 VA
2 E 0.5 - 1.0 A 144 12.0 A 1.5 A 8.5 VA
3 F 1.0 - 2.0 A 625 25.0 A 3 A 8.5 VA
4 G 2.0 to 4.0 A 2500 50.0 A 6 A 8.5 VA
5 H 4.0 to 8.0 A 10000 100 A 12 A 8.5 VA
6 J 8.0 - 16.0 A 40000 200 A 20 A 9.5 VA
F, G, or H
†
7 K 16.0 - 32.0 A 90000 300 A 20 A 14.0 VA
2 E 0.25 - 2.0 A 10000 100 A 5 A 0.2 VA
4 G 1.0 - 8.0 A 90000 300 A 10 A 0.6 VA
O, P, R, S,
or T
6 J 4.0 - 32.0 A 90000 300 A 20 A 4.8 VA
∗ Ratings other than continuous may be calculated using the equation:
where:
t
K
I =
K =
T =
I =
the indicated value
the time in seconds
maximum current
† Power Supply types F, G, and H are no longer available.
Pickup Range
Continuously adjustable over the range defined by the style number with independent ranges and
adjustments for each phase and neutral pickup.
Pickup Accuracy
±2% or ±40 mA of pickup setting, whichever is greater.
Dropout
Within 2% of pickup.
Timing
1.5 cycles or less from onset of overcurrent condition. (30 milliseconds at 50 Hz, 25 milliseconds at 60
Hz.)
Output Contacts
Resistive Ratings
120 Vac: Make, break, and carry 7 Aac continuously
250 Vdc: Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
500 Vdc: Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc: Break 0.3 A (L/R = 0.04)