2-2 BE1-50 Controls and Indicators 9171000990 Rev E
Locator Description
E
Target Indicators. These electronically latched red target indicators illuminate when the
corresponding output relay energizes. To ensure proper operation of the current-operated
targets, the current flowing through the trip circuit must be 200 mA or higher. The target
indicators are reset by operating the target reset switch (locator D).
F
Output Test Pushbuttons. These pushbuttons allow manual actuation of the output relays.
Output relay actuation is achieved by inserting a nonconductive rod through the front
panel access hole.