9469300994 2-7
DGC-2020HD Terminals and Connectors
Note
It is recommended in all applications where contact outputs drive relay
coils that a reverse biased diode be implemented in parallel with the
relay coil for EMI suppression.
Programmable Output Contacts Rated for 2-Ampere Duty
Twelve programmable output contacts rated for 2-ampere duty are provided in four sets. Each set of
three output contacts shares a common terminal. Programmable output contact terminals are listed in
Table 2-11.
Table 2-11. Programmable Output Contact Terminals
Terminal
Description
15 (OUT 1)
Programmable output 1
16 (OUT 2)
Programmable output 2
17 (OUT 3)
Programmable output 3
18 (COM 1, 2, 3)
Common connection for outputs 1, 2, and 3
19 (OUT 4)
Programmable output 4
20 (OUT 5)
Programmable output 5
21 (OUT 6)
Programmable output 6
22 (COM 4, 5, 6)
Common connection for outputs 4, 5, and 6
23 (OUT 7)
Programmable output 7
24 (OUT 8)
Programmable output 8
25 (OUT 9)
Programmable output 9
26 (COM 7, 8, 9)
Common connection for outputs 7, 8, and 9
27 (OUT 10)
Programmable output 10
28 (OUT 11)
Programmable output 11
29 (OUT 12)
Programmable output 12
30 (COM 10, 11, 12)
Common connection for outputs 10, 11, and 12
CAN Interface
These terminals provide communication using the SAE J1939 protocol or the mtu protocol and provide
high-speed communication between the DGC-2020HD and an ECU on an electronically controlled
engine. Connections between the ECU and DGC-2020HD should be made with twisted-pair, shielded
cable. CAN interface terminals are listed in Table 2-12. For typical CAN connections, refer to the Typical
Connections chapter.
Table 2-12. CAN Interface Terminals
Terminals
Description
51 (CAN 1 L)
CAN 1 low connection
52 (CAN 1 H)
CAN 1 high connection
53 (SHIELD)
CAN drain connection
54 (CAN 2 L)
CAN 2 low connection
55 (CAN 2 H)
CAN 2 high connection