DGC-2020HD Terminals and Connectors
Terminal
Description
67 (GOV –)
GOV control output negative
68 (GOV PWM)
GOV PWM output for CAT control system interface
Load Share Line
Load share line outputs are measured and used to calculate the per-unitized average load level. This
average is used as the setpoint for the genset’s kW controller. Load share line output terminals are listed
in Table 2-16.
Table 2-16. Load Share Line Output Terminals
Terminal
Description
69 (LOAD SHARE +)
Load share line positive
70 (LOAD SHARE –)
Load share line negative
IRIG-B Connections
The IRIG-B terminals connect to an IRIG-B source for synchronization of DGC-2020HD timekeeping with
the IRIG-B source. Table 2-17 lists the IRIG-B source input terminals.
Table 2-17. IRIG-B Source Input Terminals
Terminal
Description
59 (IRIG-B +)
IRIG-B source input
60 (IRIG-B –)
IRIG-B return terminal
Optional Remote Display Panel Connections
Terminals are provided for connection with the optional remote display panel (Basler P/N 9318100114
projection mount or 9318100115 flush mount). These terminals provide dc control power to the remote
display panel and enable communication between the DGC-2020HD and the remote display panel.
Twisted-pair conductors are recommended for making the connections between the DGC-2020HD and
remote display panel. Communication may become unreliable if the connection wires exceed 1,219 m
(4,000 ft). Table 2-18 lists the DGC-2020HD terminals that connect to the remote display panel.
Table 2-18. Remote Display Panel Interface Terminals
Terminal
Description
61 (RDP TxD +)
Remote display panel communication terminal (TxD +)
62 (RDP TxD –)
Remote display panel communication terminal (TxD –)
49 (BATT–)
Remote display panel power terminal DC COM (–)
48 (BATT+)
Remote display panel power terminal 12/24 (+)
Connectors
USB Interface
A mini-B USB jack enables local communication with a PC running BESTCOMSPlus
®
software. The
DGC-2020HD is connected to a PC using a standard USB cable equipped with a type A plug on one end
(PC termination) and a mini-B plug on the other end (DGC-2020HD termination).
Ethernet Communications
Dual copper RJ-45 jacks or an ST fiber optic port provide Ethernet communications between the DGC-
2020HD and a PC via BESTCOMSPlus or other DGC-2020HDs in a network. The ST type fiber optic port
uses a 1,300 nanometer, near-infrared (NIR) light wavelength transmitted via two strands of multimode
optical fiber, one for receive (RX) and the other for transmit (TX).