9469300994 3-11
DGC-2020HD Typical Applications
To achieve electromagnetic interference immunity on the analog inputs, clamp two ferrite beads (Fair-Rite
P/N 0431176451) in series around all of the wires. Place the ferrite beads close to the DGC-2020HD
analog input terminals.
Analog Voltage Input Connection
Figure 3-21. Analog Inputs, Voltage Input Connections
Analog Current Input Connections
Figure 3-22. Analog Inputs, Current Input Connections, Type II 2-Wire Current Loop Circuit